Vaillant VU 446/5-5 / VU 606/5-5 fault F.75
Pump fault/water deficiency
Gas boilerWhat it means
A pump malfunction or water deficiency has been detected. Further diagnosis available via diagnostics code D.149.
Likely causes
- Pump blocked
- Electrical pump fault
- Pump dry run
- Pressure sensor fault
- No feedback from the pump
- Incorrect pump detected
- Flow rate at the end of the purge programme is insufficient
- Closed stopcocks in the hydraulic installation
- Closed thermostatic valves on radiators
- Insufficient filling pressure in the heating installation
- Air remaining in the system preventing adequate flow
- Malfunction
- D.149 = 1, pump blocked alarm
- Defective pump
Where to start
- Read parameter D.149 to determine the specific circulation fault value
- Match D.149 value to the corresponding cause from the list: 0=No fault, 1=Pump blocked, 2=Electrical pump fault, 3=Pump dry run, 5=Pressure sensor fault, 6=No feedback from the pump, 7=Incorrect pump detected, 8=Flow rate at end of purge programme insufficient
- Ensure that all of the stopcocks in the hydraulic installation are open
The full answer, free
- 9 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 62), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
From the Vaillant manual for the VU 446/5-5 / VU 606/5-5. Check the model on the data plate before you order parts.
Other Vaillant VU 446/5-5 / VU 606/5-5 fault codes
- F.00Flow temperature sensor interruption
- F.01Return temperature sensor interruption
- F.03Cylinder temperature sensor interruption
- F.10Flow temperature sensor short circuit
- F.11Return temperature sensor short circuit
- F.13Cylinder temperature sensor short circuit
- F.22Safety shutdown: water deficiency
- F.23Safety shutdown: temperature spread too great
- F.24Safety shutdown: temperature rise too fast
- F.25Safety shutdown: flue gas temperature too high
- F.27Safety shutdown: flame simulation
- F.32Fan fault
- F.33Air pressure switch fault
- F.64Fault: electronics/NTC
- F.65Electronics temperature fault
- F.72Flow and/or return temperature sensor fault
- F.74Water pressure sensor signal outside correct range (too high)
- F.77Accessory fault (flue non-return flap, condensate pump, etc.)
- F.83Flow and/or return temperature sensor temperature change fault
- F.84Temperature difference fault at the flow and return temperature sensors
- F.85Flow and return temperature sensors installed incorrectly (inverted)
- P.02Minimum load check programme
- S.42Flue non-return flap closed
- S.46Comfort protection: minimum load, loss of flame